CSA C282 - Monthly (Weekly in health care facilities) inspection, test, and maintenance requirements
(See Clauses 6.7, 10.7, 11.1.2, 11.4, 11.5.1, and 11.5.2 and Tables 4 and 5.)
1. Complete all items specified in Table 2.
2. Test and verify the entire system as follows:
(a) Simulate a failure of the normal electrical supply to the building.
(b) Verify that the battery charger current output increases while cranking.
(c) Operate the system under at least 30% of the rated load for 60 min.
(d) Operate all automatic transfer switches under load.
(e) Inspect brush operation for sparking.
(f) Inspect for bearing seal leakage.
(g) Inspect for correct operation of all auxiliary equipment, e.g., radiator shutter control, coolant pumps, fuel transfer pumps, oil coolers, and engine room ventilation system(s).
(h) Record the readings for all instruments in the log (see Clause 11.5.3) and verify that they are normal.
(i) Drain the exhaust system condensate trap.
|
|
Please take your time and familiarize yourself with the requirements of each testing requirements |
|
3. Inspect block heater hoses and wires.
4. Correct all defects found during inspections and tests.
5. Record all inspections, tests, and corrective actions in the log (see Clause 11.5.3).
6. Inspect all electrical components to ensure proper function.
Note: The work described in this Table shall be carried out by a competent person, or individuals trained by the system manufacturer.
|